Testing
Output : 0-40kV(negative wrt earth)25mA constant
Resolution : 1mA
Trip : adjustable current trip
Metering : analogue and digital metering of current and voltage
Pre-location low voltage prelocation
MTDR
Range : 60m-50km
Pulse width : 40, ,80, 160, 320, 640 ns 1, 2, 5, 1μs, and auto
Display : 8in/, full VGA, colour
Cursors : Dual independent control
Gain : Auto and selectable x1, 2, 3, 4, 5, 10, 20, 50, 100
Input : Impedance 50Ω
Inputs : 1 pulse echo, 1 current impulse/voltage decay
Ports : 1 serial, 2 parallel (printer/USB memory device)
High voltage prelocation
Arc reflection : 8/16/34kV
1500 or 2000 joule
4kV at 1500 joules(optional)
ICE : 8/16/34Kv
4kV at 1500 joules(optional)
Voltage decay : 0-40kV (optional)
Fault conditioning
Arc reflection : 8/16/34kV(optional4kV)
Proof/burn : 0-40kV
0-8kV, 120mA
0-16kV, 60mA
0-34kV, 30mA
0-4kV, 240mA(optional)
Pinpoint fault location
Surge : 0-8/16/34kV
0-4kV at 1500 joules(optional)
1500/2000 joules(dependant on model)
Impulse sequence : adjustable 2-12 seconds signal shot
Cables
HV : 15m of 70kV 1-phase EPR
Input/supply : 15m, 8mm2
Earth : 15m, 8mm2
Earth monitor : 15m